GF312D1 HANDHELD THREE PHASE ENERGY METER CALIBRATOR / Data Sheet : Download / Main Catalogs : Download
The instrument is a precision AC energy meter testing instrument, mainly used to test three phase energy meter error on site and measure all various of AC parameters.
FEATURES AND FUNCTIONS
- Three phase active or reactive electricity energy meter.
- Calibrate three phase, single phase, and active or reactive meter error.
- Measure U(voltage) of three phase or single phase.
- Measure I(current) of three phase or single phase.
- Measure active power of three phase or single phase.
- Measure reactive power of three phase or single phase.
- Measure apparent power of three phase or single phase.
- Measure power factor of three phase or single phase.
- Measure phase angle between voltage and current.
- Measure frequency of power line.
- Display vector diagram.
- Display waveform of U and I.
- Analyze and display content of harmonic of U and I.
- Measure 2-64 harmonic of U, I.
- Store and display measured data.
- Optional 5A, 20A, 100A, 500A, 1000A, 2000A, 3000A current clamp.
- Measure CT variable ratio.
- Measure the ratio or lag-angle of low-voltage transformer.
- Adopt 32 bit ARM processor, multi-channel 16 bit precision A/D convertor, high resolution TFT color LCD.
- Inner equipped with 0.01% wide-range current transformer and can be equipped with various type current clamps, wide range of measurement and high veracity.
- Low consumption circuit design, high energy Lithium battery supply, intellectual power management software, which enables the instrument continuously working up to 10 hours.
Electrical parameters
- Accuracy class : 0.05%, 0.1%
- Resolution : 6”TFT (640×480)
- Power supply : 220V±10%, 50/60Hz
- Li-polymer battery (size (mm): 110x51x16, nominal output voltage: 7.2V, capacity: 5000mAh) Power line supply (U1, UN), 85V-265V 50/60Hz
- Communication port : RS232
Test voltage
- Range : 0-480V
- Error : ±0.05% (30V-480V) : ±0.1% (5V-30V)
- Harmonic : 2nd-64st
Test current
- Range (direct connection) : 5mA-20A
- Error (direct connection) : ±0.05% (100mA-20A) , ±0.1% (10mA-100mA)
- Range (clamp CT) : 10mA-3000A
- Error (camp CT) : ±0.2% (100mA-100A) , ±0.5% (100A-3000A)
- Harmonic : 2nd-64st
Power measure error
- Active power (direct connection) , ±0.05% (0.1A-20A) , ±0.1% (0.01A-0.1A)
- Reactive power (direct connection) : ±0.1% (0.1A-20A)
Energy measure error
- Active energy (direct connection) : ±0.05% (0.1A-20A) , ±0.1% (0.01A-0.1A)
- Reactive energy (direct connection) : ±0.1% (0.1A-20A)
Phase angle
- Range : 0°-360°
- Resolution : 0.01o
- Error : ±0.05°
Frequency
- Range : 45-65Hz
- Resolution : 0.001Hz
- Error : 0.002Hz
Pulse input
- Input channel : 2
- Input level : 5-24V
- Input frequency : Max. 2MHz
Pulse output
- Energy constant : 180000imp/kWh, 1800imp/kWh, 180imp/kWh
- Pulse ratio : 1:1
- Output level : 5V
Function
- Vector diagram : Yes
- Waveform : Yes
- Energy accumulation : Yes
- Communication with PC :Yes
Mechanical parameters
- Instrument dimensions (W×H×D) (mm) : 245×162×60
- Instrument Weight (kg) : 1.8
- Carry case dimensions (W×H×D) (mm) : 450×320×185
- Carry case (kg) : 10.6
Environmental conditions
Ambient temperature : -10°C to 55°C
Relative humidity : 15%-85%
MOQ. 1Ea.